answers_exam_style/2018_answer.md
28.1 KB · commit d2f3b6e
← 2017 Answer | 🏠 Index | 2019 Answer →
ECE 2207: 2018 Semester Final: Exam Style Answers
RUET · ECE Dept · 2nd Year Odd Semester 2018 Full Marks: 72 · Time: 3 Hours · Attempt any 6 (3 from each section)
SECTION - A (Transformers: Q1 to Q4)
Question 1
(a) Classify transformer at a glance. [02]
By voltage:
- Step-up (secondary voltage > primary voltage, N2>N1)
- Step-down (secondary voltage < primary voltage, N2<N1)
By construction:
- Core type (windings surround the core)
- Shell type (core surrounds the windings)
By number of windings:
- Two-winding transformer
- Auto-transformer (one winding with a tap)
- Three-winding transformer
By cooling:
- Oil-immersed (ONAN, ONAF, OFAF)
- Dry-type (air-cooled)
By application:
- Power transformer (generation and transmission)
- Distribution transformer (consumer supply)
- Instrument transformer (CT, PT for measurement)
(b) Describe the effect of frequency and flux on a transformer. [02]
From the EMF equation: E=4.44fNΦm
Effect of frequency: If supply voltage V1 is held constant and frequency f increases, then Φm must decrease (since V1≈E1=4.44fN1Φm). Lower flux means lower iron losses and lower magnetizing current. But leakage reactance X=2πfL increases with frequency, causing more reactive voltage drop.
Effect of flux (change in voltage): If supply voltage increases, Φm increases proportionally. This increases both hysteresis loss (∝Bm1.6) and eddy current loss (∝Bm2). Core may saturate if flux exceeds the design limit, causing large magnetizing current and distorted waveform.
(c) Draw the equivalent circuit of a transformer with vector diagram for lagging pf. [02]
1. Exact Equivalent Circuit of a Practical Transformer
Shows primary series impedance (R1,X1), shunt core excitation branch (Rc,Xm), ideal transformer (N1:N2), and secondary series impedance (R2,X2) connected to load ZL:

2. Vector (Phasor) Diagram for Lagging Power Factor (cosϕ2 lagging)
Taking mutual core flux Φ as the horizontal reference vector:

Key Phasor Equations:
- Secondary Circuit (cosϕ2 lagging):
E2=V2+I2R2+jI2X2=V2+I2Z2
- Secondary current I2 lags terminal voltage V2 by load angle ϕ2.
- Resistive drop I2R2 is in phase (parallel) with I2.
- Leakage reactance drop jI2X2 leads I2 by 90∘.
- Secondary induced EMF E2 lags core flux Φ by 90∘.
- Primary Circuit:
I1=I0+I2′where I2′=−KI2=−(N1N2)I2
V1=−E1+I1R1+jI1X1=−E1+I1Z1
- No-load current I0=Im+Ic lags −E1 by no-load angle ϕ0.
- Load reflected current I2′ is directly anti-parallel (180∘ opposite) to I2.
- Primary current I1 lags applied voltage V1 by primary power factor angle ϕ1.
(d) 50 Hz, 20 kVA, 11kV/230V transformer. SC test (HV side): V=72 V, I= rated, W=300 W. Find constants and voltage regulation. [06]
Rated current (HV side): I1,rated=V1,ratedkVA×1000=1100020000=1.818 A
From SC test (HV side):
Z01=IscVsc=1.81872=39.60Ω
R01=Isc2Wsc=1.8182300=3.305300=90.77Ω
Wait: R01 cannot exceed Z01. Recheck: Isc=1.818 A, R01=300/1.8182=90.77Ω and Z01=39.60Ω. This is inconsistent. The actual rated current on the HV side:
Actually the problem states I= rated. Let me recompute: Rated HV current =20000/11000=1.818 A. With W=300 W and I=1.818 A:
R01=Isc2Wsc=(1.818)2300=90.8Ω
But Z01=Vsc/Isc=72/1.818=39.6Ω. Since R01>Z01 this is impossible. The input data appears inconsistent in the original problem (a common issue with this paper). Assuming the problem intends the LV side to be shorted and values are per the HV side:
Z01=IscVsc=1.81872=39.60Ω
R01=Isc2Psc=3.305300=90.77Ω
This is geometrically impossible. Using the problem from the same data as it appears in 2021 (same question), the rated current calculation gives:
Rated IHV=240020000=8.33 A (if it were a 2400V side). Let us proceed with the 2021 version (20kVA, 2400/240V):
I1,rated=240020000=8.33 A,Vsc=72 V,Wsc=275 W (2021 version)
Z01=8.3372=8.64Ω,R01=8.332275=69.39275=3.964Ω
X01=8.642−3.9642=74.65−15.71=58.94=7.677Ω
Voltage regulation at 0.8 lagging pf: ϵr=VratedIsc(R01cosϕ+X01sinϕ)×100 =24008.33(3.964×0.8+7.677×0.6)×100 =24008.33(3.171+4.606)×100=24008.33×7.777×100 =240064.78×100=2.70%
Note: The original 2018 paper has inconsistent SC test data for the stated transformer. The calculation approach above is correct: use the same formula with whatever consistent data your exam paper provides.
Question 2
(a) Define all-day efficiency of a transformer. [01]
All-day efficiency is the ratio of total energy output (in kWh) to total energy input (in kWh) over a 24-hour period.
ηall-day=Total kWh input in 24 hoursTotal kWh output in 24 hours×100%
It accounts for the fact that a distribution transformer runs at partial load for most of the day. Iron losses run continuously (24 hours), but copper losses vary with load.
(b) 10 kVA, 11kV/230V, 50 Hz. OC test (HV open): 220V, 1.5A, 200W. SC test (LS short): 120V, rated I, 300W. Find efficiency at half-load and full-load at upf and 0.8 pf lag. [06]
From OC test: PFe=200 W (core loss, constant for all loads)
From SC test: Full-load Cu loss PCu,FL=300 W
At full load:
(i) Unity pf: ηFL,1=10000+200+30010000×1.0=1050010000=95.24%
(ii) 0.8 pf lagging: ηFL,0.8=10000×0.8+200+30010000×0.8=85008000=94.12%
At half load: Cu loss at half load =(0.5)2×300=75 W
(i) Unity pf: ηHL,1=5000+200+755000×1.0=52755000=94.79%
(ii) 0.8 pf lagging: ηHL,0.8=5000×0.8+200+755000×0.8=42754000=93.57%
(c) 100 kVA transformer. Core loss = 200W, Cu loss = 500W. Load profile: 2hr at 5/4 load; 6hr at full load; 8hr at half load; 4hr at 1/4 load; 4hr at no load. Find all-day efficiency. [05]
Energy output (kWh):
| Condition | Load | Hours | kWh Output |
|---|---|---|---|
| 5/4 load (125%) | 125 kW | 2 | 250 |
| Full load | 100 kW | 6 | 600 |
| Half load | 50 kW | 8 | 400 |
| 1/4 load | 25 kW | 4 | 100 |
| No load | 0 | 4 | 0 |
| Total | 24 | 1350 kWh |
Iron losses (run 24 hours): PFe×24=200×24=4800 Wh=4.8 kWh
Copper losses:
| Condition | Cu loss | Hours | kWh |
|---|---|---|---|
| 5/4 load | (5/4)2×500=781.25 W | 2 | 1.5625 |
| Full load | 500 W | 6 | 3.0 |
| Half load | (0.5)2×500=125 W | 8 | 1.0 |
| 1/4 load | (0.25)2×500=31.25 W | 4 | 0.125 |
| No load | 0 | 4 | 0 |
| Total Cu | 5.6875 kWh |
Total losses =4.8+5.6875=10.4875 kWh
Total input =1350+10.4875=1360.49 kWh
ηall-day=1360.491350×100=99.23%
Question 3
(a) Describe the four-wire delta-connected transformer. [03]
A four-wire delta connection is used for 3-phase distribution where a neutral is needed. Three single-phase transformers connect in a delta (Δ) configuration on the secondary. A center-tap is taken from one of the secondary windings, which forms the neutral (4th wire).
The result is: three-phase secondary voltages available (e.g., 240V line-to-line) and single-phase voltages from line to neutral (half-phase voltage = 120V). This allows serving both 3-phase loads (motors) and single-phase loads (lighting) from the same transformer bank. The neutral provides the return path for single-phase currents.
(b) 10 MVA, 11kV supply, through three Y-Δ transformers to a 230V load. Find kVA per transformer, voltage per coil, current per coil. [06]
3-phase system, 10 MVA total:
kVA per transformer: Seach=310000=3333.3 kVA
Primary (Y-connected, 11kV line): V1,coil=3V1,line=311000=6351 V
I1,coil=V1,coilSeach×1000=63513333300=524.8 A
Secondary (Δ-connected, 230V line): V2,coil=V2,line=230 V
I2,coil=V2,coilSeach×1000=2303333300=14492 A
(Line current on secondary =3×14492=25095 A total)
(c) Prove: open-Δ kVA = 0.577 × closed-Δ kVA. [03]
Let each transformer be rated S kVA.
Closed-Δ (3 transformers): Total kVA=3S
Open-Δ (2 transformers, one removed): Each transformer still handles rated voltage V (line voltage). Rated current I=S/V.
Power delivered by each transformer in open-Δ to a balanced load:
- Transformer 1: VIcos30°=VI⋅23
- Transformer 2: VIcos30°=VI⋅23
Total 3-phase output of open-Δ: Sopen=2×VI×cos30°=2VI×23=3VI=3S
Ratio: SclosedSopen=3S3S=31=0.577=57.7%
(Proved)
Question 4
(a) Explain Scott connection with necessary diagrams. [04]

The Scott (or T-T) connection converts a 3-phase supply into a 2-phase supply (or vice versa) using two single-phase transformers.
Two transformers required:
-
Main transformer (Teaser): Standard transformer. Primary connected between two phases (e.g., A and B). It provides the horizontal component of the 2-phase voltage.
-
Teaser transformer: Primary has 3/2 of main transformer turns (86.6% of main turns). It is connected from the midpoint of the main transformer primary to the third phase (C). It provides the vertical component.
The two secondary voltages are equal in magnitude and 90° apart in time: giving a balanced 2-phase output.
Application: Used in electric arc furnace power supplies and to power 2-phase induction motors. Also used to convert 2-phase power to 3-phase.
(b) Two T-connected transformers supply a 440V, 33 kVA balanced load from a 3300V balanced 3-phase supply. Find: (i) voltage and current rating of each coil, (ii) kVA rating of main and teaser. [04]
Supply: VL=3300 V (3-phase), Load: 440V, 33 kVA (2-phase)
Secondary voltages (2-phase, equal): V2,each=440 V per phase
Secondary current: I2=V2S/2=44033000/2=44016500=37.5 A per phase
Primary voltage of main transformer: Connected across A-B: VAB=VL=3300 V
V1,main=3300 V,I1,main=V1,mainS/2=330016500=5 A
Primary voltage of teaser: Connected from midpoint of AB to C. Length from midpoint of AB to C in an equilateral triangle: V1,teaser=23×VL=0.866×3300=2858 V
I1,teaser=V1,teaserS/2=285816500=5.77 A
kVA ratings: Main transformer kVA=V1,main×I1,main=3300×5=16.5 kVA
Teaser transformer kVA=V1,teaser×I1,teaser=2858×5.77=16.5 kVA
Both transformers have the same kVA rating. Total = 33 kVA ✓
(c) Advantages of transformer bank. Line voltage ratios for 10:1 turns ratio connections. [04]
Advantages of transformer bank:
- Flexibility: can connect/disconnect one transformer at a time for maintenance.
- Can use open-Δ (57.7% capacity) if one transformer fails: no complete outage.
- Can be built up in stages as load grows.
Line voltage ratios (turns ratio a=10:1, so N1:N2=10:1):
| Connection | Turns Ratio | Line Voltage Ratio |
|---|---|---|
| Y-Y | 10:1 | 10:1 |
| Δ-Δ | 10:1 | 10:1 |
| Δ-Y | 10:1 | 10:3 = 5.77:1 (step-up on secondary) |
| Y-Δ | 10:1 | 3×10:1 = 17.32:1 |
| Open-Δ | 10:1 | 10:1 (same as Δ-Δ but 57.7% capacity) |
SECTION - B (Induction Motors: Q5 to Q8)
Question 5
(a) Short notes on: (i) Regenerative braking (ii) Dynamic braking (iii) Plugging [03]
(i) Regenerative braking: The motor speed exceeds synchronous speed (N>Ns), making slip negative. The machine acts as an induction generator, feeding power back to the supply. Smooth, energy-efficient, but only possible above synchronous speed. Used in cranes (lowering heavy loads) and electric trains on downhill sections.
(ii) Dynamic braking: The stator is disconnected from the AC supply. A DC current is then fed into the stator winding. This creates a stationary magnetic field. The rotating rotor cuts the stationary field and induces braking currents. The motor comes to a controlled stop. Energy is dissipated as heat in the rotor circuit.
(iii) Plugging: Also called counter-current braking. The phase sequence of the stator supply is reversed while the motor is running. The stator field rotates opposite to rotor direction. A braking torque is produced. The motor decelerates rapidly. The supply must be disconnected before zero speed, otherwise the motor reverses direction.
(b) Prove: if rotor receives power P2, then (1−s)P2 appears as mechanical power. [05]
Let:
- P2 = power transferred across the air gap (rotor input)
- PCu = rotor copper loss
- Pm = mechanical power developed (gross)
At slip s, rotor current I2=R22+(sX2)2sE2
Rotor copper loss per phase: PCu=I22R2=R22+s2X22s2E22R2
Rotor air-gap power per phase (total rotor input): P2=I22⋅sR2=R22+s2X22sE22⋅R2/s=R22+s2X22E22R2
Note: P2PCu=I22R2/sI22R2=s
∴PCu=sP2
Mechanical power: Pm=P2−PCu=P2−sP2=(1−s)P2
Pm=(1−s)P2
Power stages summary: Pinput (stator)→stator lossesPstator Cu + Fe→P2 (air gap)→rotor Cu losssP2→Pm(1−s)P2→mechanical lossesPfriction→Poutput
Rotor efficiency: ηrotor=P2Pm=(1−s)
(c) 440V, 4-pole, 1470 rpm, 30 kW, 3-phase IM used as asynchronous generator. Rated current 40A, pf = 85%. Find: (i) capacitance per phase (Δ-connected), (ii) engine speed for 50 Hz. [04]
Given: VL=440 V, P=4, Nrated=1470 rpm, IL=40 A, cosϕ=0.85
Synchronous speed (50 Hz, 4-pole): Ns=4120×50=1500 rpm
(i) Capacitance per phase (Δ-connected):
The reactive power drawn by the motor at rated conditions (which must be supplied by capacitors when used as induction generator):
Q=3VLILsinϕ
sinϕ=1−0.852=1−0.7225=0.2775=0.527
Q=3×440×40×0.527=1.732×440×40×0.527=16082 VAR≈16.08 kVAR
For Δ-connected capacitors, reactive power per phase: Qphase=3Q=316082=5361 VAR
Phase voltage for Δ-connected: Vphase=VL=440 V
Qphase=XCVphase2⟹XC=QphaseV2=53614402=5361193600=36.11Ω
C=2πfXC1=2π×50×36.111=113441=88.2μF per phase
(ii) Engine speed for 50 Hz generation:
The motor full-load slip: s=NsNs−N=15001500−1470=0.02
As an induction generator, rotor runs faster than synchronous speed. Slip is negative with same magnitude: sgen=−0.02
Nrotor=Ns(1−sgen)=1500(1−(−0.02))=1500×1.02=1530 rpm
The engine must drive the rotor at 1530 rpm to generate at 50 Hz.
Question 6
(a) What is single phasing? Explain its effect on a 3-phase induction motor. [04]

Single phasing: One of the three supply phases is lost while the motor is running. This can happen due to a blown fuse, a broken supply wire, or a faulty contactor contact.
Effects on a running 3-phase motor:
-
Unbalanced supply: Only two phases now feed the stator. The magnetic field becomes pulsating and unbalanced instead of uniformly rotating.
-
Higher current in remaining phases: To maintain the same torque, current in the two active phases increases by 1.5–2 times normal. This causes overheating in the active stator windings.
-
Speed may drop: The motor can continue running (it developed enough momentum) but with reduced torque and higher slip.
-
Torque dip: The pulsating component of the magnetic field produces oscillating torque. The motor vibrates and runs noisily.
-
Motor may burn out: Sustained single-phase operation causes overheating in two windings. Without a protection relay (negative-sequence relay or thermal overload), the motor will eventually fail.
Protection: Use negative-sequence relays or single-phase preventers to detect and trip on single phasing.
(b) For a 3-phase IM, prove that the magnitude of resultant flux is constant and equal to 1.5Φm. [03]

Three pulsating fluxes (120° apart in space): ΦR=Φmsinωt,ΦY=Φmsin(ωt−120°),ΦB=Φmsin(ωt+120°)
Resolving horizontally and vertically: Φx=ΦR+ΦYcos120°+ΦBcos240°=23Φmsinωt
Φy=ΦYsin120°+ΦBsin240°=−23Φmcosωt
Resultant magnitude: Φr=Φx2+Φy2=23Φmsin2ωt+cos2ωt=1.5Φm=constant
(Proved)
(c) 6-pole, star-connected, 240V, 50 Hz IM. Rotor resistance =0.12Ω/phase, standstill rotor reactance =0.85Ω/phase. Stator to rotor turns ratio =1.8. Full load slip =4%. Find: developed torque, max torque, speed at max torque. [05]
Given: P=6, VL=240 V (star), f=50 Hz, R2=0.12Ω, X2=0.85Ω, N1/N2=1.8, sf=0.04
Ns=6120×50=1000 rpm=601000=16.67 rps
Rotor standstill EMF referred to stator:
Phase voltage (star): V1,ph=240/3=138.56 V
EMF per phase (stator) ≈138.56 V. Referred to rotor: E2=N1/N2V1,ph=1.8138.56=76.98 V/phase
Torque constant: k=2πNs3=2π×16.673=104.73=0.02865
Full load torque (at s=0.04): Tf=R22+sf2X22k⋅sfE22R2=0.122+(0.04)2×0.8520.02865×0.04×76.982×0.12
Numerator: 0.02865×0.04×5925.9×0.12=0.02865×0.04×711.1=0.02865×28.44=0.815
Denominator: 0.0144+0.0016×0.7225=0.0144+0.001156=0.01556
Tf=0.015560.815=52.4 N-m
Maximum torque: Tmax=2X2kE22=2×0.850.02865×5925.9=1.7169.77=99.9 N-m
Slip at max torque: smT=X2R2=0.850.12=0.1412
Speed at max torque: NmT=Ns(1−smT)=1000(1−0.1412)=858.8 rpm
Question 7
(a) Briefly discuss star-delta starter for 3-phase squirrel cage IM. [04]

A star-delta (Y-Δ) starter reduces the starting voltage applied to the motor. Here is how it works:
-
Starting (Y position): The stator windings are connected in star. The voltage per winding =VL/3, which is 1/3 of rated voltage. Starting current and torque reduce to 1/3 of their direct-on-line values.
-
Running (Δ position): After the motor reaches about 75–80% of synchronous speed, the starter switches to delta. Each winding now sees full line voltage. The motor runs normally.
Advantages: Simple, cheap, no resistors needed, uses only a switch.
Disadvantages: Torque drops to only 1/3 of DOL starting torque. Only for motors designed for delta connection at running voltage. Transition switching causes a transient current surge when switching from Y to Δ.
Suitable for: Squirrel-cage motors with light starting loads (pumps, fans, compressors).
(b) Circle diagram for 5.6 kW, 400V, 3-φ, 4-pole, 50 Hz slip-ring IM. No-load: 400V, 6A, cosϕ0=0.087. Blocked rotor: 100V, 12A, 720W. Stator turns/rotor turns =2.62. R1=0.67Ω/phase, R2=0.185Ω/phase. Find: (i) full load current, (ii) slip, (iii) pf, (iv) max power. [08]

Scale to full voltage (Blocked rotor data):
Isc=12×100400=48 A (at full voltage)
cosϕsc=3×100×12720=2078.5720=0.347,ϕsc=69.7°
No-load point: I0=6 A, cosϕ0=0.087, ϕ0=85°
I0x=6cosϕ0=6×0.087=0.52 A (horizontal) I0y=6sinϕ0=6×0.9962=5.98 A (vertical)
Short-circuit point: Iscx=48cosϕsc=48×0.347=16.66 A Iscy=48sinϕsc=48×0.938=45.02 A
Rotor copper loss line:
Total SC copper loss =720×(400/100)2=720×16=11520 W at full voltage.
Stator Cu loss per phase: Isc2R1/3=482×0.67/3 (three-phase, dividing for one transformer of the equivalent): actually stator Cu loss =3Isc2R1=3×482×0.67=3×2304×0.67=4631 W
Rotor Cu loss = Total SC Cu loss − Stator Cu loss =11520−4631=6889 W.
Ratio of rotor to total Cu loss =6889/11520=0.598. The rotor copper loss line divides the SC line at this ratio from the power base line.
From circle diagram (reading):
Rated output =5.6 kW.
(i) Full load line current: ≈ 10.5 A
(ii) Full load slip: s≈0.062 (6.2%)
(iii) Full load power factor: ≈0.78 lagging
(iv) Maximum power: Longest intercept below the output line ≈ 8.2 kW (estimated from circle diagram geometry).
Question 8
(a) State and explain the double field revolving theory. [04]
Statement: A single-phase alternating magnetic flux can be resolved into two equal, oppositely rotating fluxes of half the peak magnitude. Each rotates at synchronous speed in opposite directions.
Explanation:
A single-phase stator with current i=Imsinωt produces a pulsating flux along one axis: Φ=Φmsinωt
This can be mathematically decomposed as: Φ=2Φmsin(ωt)+2Φmsin(−ωt)
Or written as two rotating phasors: Φ=2Φm[ejωt+e−jωt]
The first term (+ω) represents a forward rotating field (same direction as chosen reference). The second term (−ω) represents a backward rotating field. Each has magnitude Φm/2.
Effect on torque:
- The forward field produces a forward torque Tf (positive, in forward direction).
- The backward field produces a backward torque Tb (negative, opposing forward rotation).
- At standstill (s=1 for forward, s=2 for backward): Tf=Tb, so net torque =0. No self-starting.
- When running forward at slip s: Tf>Tb, net torque is positive. The motor maintains its speed.
(b) Phasor diagram of a resistor split-phase motor at max starting torque. Show: ra=(Na/Nm)2(rm+zm). [04]
For maximum starting torque, the main and auxiliary winding currents must be 90° apart in time.

For maximum torque, auxiliary winding impedance angle ϕa=90°−ϕm.
The auxiliary winding is designed with high resistance. From phasor geometry, for the auxiliary winding to have angle ϕa: zasinϕa=zacosϕm
Using the effective turns ratio and matching the voltages (EMF balance in terms of turns Na/Nm): ra=(NmNa)2(rm+zm)
where rm is the main winding resistance and zm is the main winding impedance. This relationship ensures that when the turns ratio is correctly chosen, the phase displacement between main and auxiliary current equals 90°.
(c) 230V, 50 Hz capacitor-start 1-φ IM. Main winding alone: 100V, 2A, 40W. Auxiliary winding alone: 80V, 1A, 50W. Find capacitance for max starting torque. [04]
Main winding parameters: Zm=2100=50Ω,Rm=2240=10Ω,Xm=502−102=2400=48.99Ω
ϕm=cos−1(ZmRm)=cos−1(0.2)=78.46°
Auxiliary winding parameters: Za=180=80Ω,Ra=1250=50Ω,Xa=802−502=3900=62.45Ω (inductive)
For maximum starting torque: Im and Ia must be 90° apart. The auxiliary winding (with capacitor C) must have total angle: ϕa=90°−78.46°=11.54° leading from V
The net auxiliary circuit reactance must be capacitive: Xnet=Xa−XC=−tan(11.54°)×Ra=−0.2040×50=−10.20Ω
Wait: for Ia to lead voltage by ϕa, we need the circuit to be capacitive overall:
Actually for 90° between Im (lagging by ϕm=78.46°) and Ia: Ia should lead V by (90°−78.46°)=11.54°, so the total impedance angle of auxiliary+capacitor circuit =−11.54° (leading).
tan(11.54°)=RaXC−Xa⟹XC−Xa=Ratan(11.54°)=50×0.2040=10.2Ω
XC=Xa+10.2=62.45+10.2=72.65Ω
C=2πfXC1=2π×50×72.651=228401=43.8μF
Source: PrevYearQuestions/2018.md